  ldx - u20 is a microprocessor controlled dc - ups rated 20 a usable in 12 v or 24 v systems. ldx - u20 monitors the voltage supplied by a dc source and in case of power failure a backup battery is connected to the load. when powered externally the unit charges the battery by an integrated battery charger supporting various battery chemistries. ? multiple protections ? integrated battery charger for 12 v or 24 v (or intermediate voltages) multi - chemistry batteries with a charging current up to 5 a ? 20 a rated load ? automatic sensing of input voltage, load current and battery current ? batt ery protection against reverse polarity connection and overcurrent ? battery health monitoring system: measuring battery internal resistance, battery temperature, charge/discharge cycles and coulomb counter ? user settable maximum backup time ? remote input to i nhibit the ups function ? connection for a battery thermal sensor (optional) ? industrial machine control ? 4 keys and 1 color graphic cstn lcd display ? allows online device configuration ? displays the ldx - u20 status and alarms ? usb communication port for remote monitoring and configuration ? dry contacts ? connection through usb interface ? remote monitoring and configuration ? firmware upgrade ? same functionalities of the embedded user interface w ith the ease of the pc benefits
2 ldx - u20 tech.support@psbel.com ldx - u20 11 - 28 v dc (10 - 29 v dc ) 20 a 12 v or 24 v 5 a input voltage (range) rated 11 - 28 v dc (10 - 29 v dc ) input current rated 20 a no load power consumption < 3 w rated battery voltage other voltages possible by request 12 v or 24 v battery chemistries lead - acid (charging voltage is temperature corrected with 3 mv/k/cell) ni - mh / ni - cd li - ion / lifepo 4 maximum battery charge current 5 a allowed battery capacity up to150 ah maximum battery current 20 a (up to 35 a for 5 seconds) load to battery switch time < 5 usec battery protections overcurrent deep discharge reverse polarity battery health monitor battery internal resistance range using kelvin connection 1 - 300 m 1.5 inch color graphic lcd used to indicate the units status and to access the configuration menus
ldx - u20 3 asia - pacific +86 755 298 85888 europe, middle east +353 61 225 977 north america +1 408 785 5200 ? 2016 bel power solutions & protection bcd.00 849 _ a a efficiency power loss at full load (on power supply) > 97.5% < 13 w efficiency power loss at full load(on battery) > 96.5% < 18 w battery charger efficiency power loss > 90% < 16 w maximum backup time user programmable or up to battery discharge threshold operating ambient temperature start - up type tested: - 40c; for temperatures < - 20c the lcd is not operating, but the unit will operate correctly. - 40c to +60c storage temperature - 20c to +60c humidity non - condensing 5 - 95% r.h. life time expectation at 25c ambient full load 253142 h (28.9 years) isolation against enclosure 0.75 kvdc cooling method natural convection cooling safety standards & approvals ul508 (reference) en60950 (reference) emc standards emission en55022: 2010 (cispr22) en55011: 2009 /a1:2010 class a class a immunity en61000 - 4 - 2:2008 en61000 - 4 - 3:2006 /a2:2010 en61000 - 4 - 4:2012 en61000 - 4 - 5:2014 en61000 - 4 - 11:2004 /a1:2010 level 3 level 3 level 3 level 1 level 2 protection degree en60529:1989 / a:2013 ip20 vibration s inusoidal iec 60068 - 2 - 6:2007 5 - 17.8 hz: 1.6 mm; 17.8 - 500 hz: 2g 2 hours / axis (x, y, z) shock iec 60068 - 2 - 27:2008 30 g 6 ms, 20 g 11 ms; 3 bumps / direction, 18 bumps total notes: ? for more details, performance and description regarding all parameters not indicated in the above table; please refer to user manual. technical parameters are typical, measured in laboratory environment at 25c, 24 v input and 24 v lead acid battery. ? power rating, losses, efficiency, ripple, thermal behaviour and s tart - up may change outside of the nominal rated input range. ? contact factory for details. ? data may change without prior notice in order to improve the product. in/battery/out connectors 2.5 mm2, pluggable screw type (24 C
4 ldx - u20 tech.support@psbel.com input / output connection : ? in (+/ - ) = connect to dc (+/ - ) power supply ? out (+/ - ) = connect to dc (+/ - ) load ? battery (+/ - ) = connect to battery (+/ - ) ? battery sense (+/ - ) = connect to battery (+/ - ) for better accuracy of internal resistance measurement ? inhibit (+/ - ) = used to inhibits the backup function ? backup = dry contact closed when ldx - u20 is running on battery ? ready = programmable dry contact weight 5 0 0 g dimensions 54 x 115 x 110 mm mounting rail iec 60715/h15/th35 - 7.5( - 15) figure 1 . mechanical dr awing
ldx - u20 5 asia - pacific +86 755 298 85888 europe, middle east +353 61 225 977 north america +1 408 785 5200 ? 2016 bel power solutions & protection bcd.00 849 _ a a configuration and diagnostic tool: ? monitors the device status ? updates the firmware ? reads and writes the device configuration ? reads and writes the configuration from/to a file ? reads the logs ? exports / imports logs from / to a file nuclear and medical applications - products are not designed or intended for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems. technical revisions - the appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. specifications are subject to change without notice.


▲Up To Search▲   

 
Price & Availability of LDX-U20

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X