  Datasheet File OCR Text:
  diesel engine-generator set 3250-XC6DT2 3250 ekw / 60 hz / standby 2800 ekw / 60 hz / prime 480 - 13.8kv a tognum g roup brand sy ste m r atings standby voltage (l-l) 480v 600v 4160v 12470v 13200v 13800v phase 3 3 3 3 3 3 pf 0.8 0.8 0.8 0.8 0.8 0.8 hz 60 60 60 60 60 60 kw 3250 3250 3250 3200 3200 3200 kva 4062.5 4062.5 4062.5 4000 4000 4000 amps 4887 3909 564 185 175 167 skva@30% voltage dip c/f c/f c/f c/f c/f c/f generator model* c/f c/f c/f c/f c/f c/f temp rise 130c/27c 125c/40c 130c/27c 130c/27c 130c/27c 130c/27c connection 6 lead wye 6 lead wye 6 lead wye 6 lead wye 6 lead wye 6 lead wye prime voltage (l-l) 480v 600v** 4160v 12470v 13200v 13800v phase 3 3 3 3 3 3 pf 0.8 0.8 0.8 0.8 0.8 0.8 hz 60 60 60 60 60 60 kw 2800 2800 2800 2750 2750 2750 kva 3500 3500 3500 3437.5 3437.5 3437.5 amps 4210 3368 486 159 150 144 skva@30% voltage dip c/f c/f c/f c/f c/f c/f generator model* c/f c/f c/f c/f c/f c/f temp rise 105c/40c 105c/40c 105c/40c 105c/40c 105c/40c 105c/40c connection 6 lead wye 6 lead wye 6 lead wye 6 lead wye 6 lead wye 6 lead wye * the generator model number identifed in the table is for standard c series confguration. consult the factory for alternate confguration. ** ul2200 ofered
2 /// / 3250-xc6 dt 2 // engine air cleaners oil pump full flow oil filter jacket water pump inter cooler water pump thermostats exhaust manifold C dry blower fan & fan drive radiator - unit mounted electric starting motor - 24v governor C electric isochronous base - structural steel sae flywheel & bell housing charging alternator - 24v battery box & cables flexible fuel connectors flexible exhaust connection epa certifed engine // g enerator nema mg1, ieee and ansi standards compliance for temperature rise and motor starting sustained short circuit current of up to 300% of the rated current for up to 10 seconds self-ventilated and drip-proof superior voltage waveform digital, solid state, volts-per-hertz regulator no load to full load regulation brushless alternator with brushless pilot exciter 4 pole, rotating field 130c standby temperature rise 2 bearings, sealed flexible coupling full amortisseur windings 125% rotor balancing 3-phase voltage sensing .25% voltage regulation 3% maximum harmonic content // d igital control panel(s) digital metering engine parameters generator protection functions engine protection sae j1939 engine ecu communications windows-based software multilingual capability remote communications to our rdp-110 remote annunciator 16 programmable contact inputs 7 contact outputs ul recognized, , ce approved event recording ip 54 front panel rating with integrated gasket nfpa110 level compatible standard equip ment // epa tier 2 certifed // engine-generator set tested to iso 8528-5 for transient response // csa listing ofered // all engine-generator sets are prototype and factory tested // mtu onsite energy is a single source supplier // global product support // 2 year standard warranty // 20v4000 g83l diesel engine - 95.4 liter displacement - common rail injection - 4-cycle // complete range of accessories // permanent magnet generator (pmg) - brushless, rotating field - 300% short circuit capability - 2/3 pitch windings // digital control panel(s) - ul recognized, , nfpa 110 - complete system metering - lcd display // cooling system - integral set-mounted - engine driven fan f acts
3 /// / 3250-xc6 dt 2 // engine manufacturer mtu detroit diesel model 20v4000 g83l type 4-cycle arrangement 20-v displacement: cu in (lit) 5,822 (95.4) bore: in (cm) 6.69 (17) stroke: in (cm) 8.27 (21) compression ratio 16.5:1 rated rpm 1,800 engine governor adec max power: standby: bhp (kwm) 4,678 (3,490) max power: prime: bhp (kwm) 4,035 (3,010) regulation .25% frequency 60 hz air cleaner dry // liquid capacity (lubrication) total oil system: gal (lit) 103 (390) engine jacket water capacity: gal (lit) 54.2 (205) after cooler water capacity: gal (lit) 14.5 (55) system coolant capacity: gal (lit) 231 (873) // electrical electric volts dc 24 cold cranking amps under 0f (-17.8c) 3,000 // fuel system fuel supply connection size 1 npt fuel return connection size 1 npt maximum fuel lift: ft (m) 3 (1) recommended fuel diesel #2 total fuel flow: gal/hr (lit/hr) 349 (1,320) // fuel consumption standby prime at 100% of power rating: gal/hr (lit/hr) 237 (897) 200 (757) at 75% of power rating: gal/hr( lit/hr) 192 (727) 149 (564) at 50% of power rating: gal/hr (lit/hr) 133 (504) 103 (390) // cooling - r adiator system standby prime ambient capacity of radiator: f (c) 108 (42) 108 (42) max. restriction of cooling air, intake, and discharge side of rad.: in. h 2 0 (kpa) 0.5 (0.12) 0.5 (0.12) water pump capacity: gpm (lit/min) 440 (1,667) 440 (1,667) after cooler pump capacity: gpm (lit/min) 163 (617) 163 (617) heat rejection to coolant: btum (kw) 83,030 (1,460) 67,675 (1,190) heat rejection to after cooler: btum (kw) 61,988 (1,090) 51,183 (900) heat radiated to ambient: btum (kw) 13,472 (237) 12,434 (218.6) // air r equirements standby prime aspirating: *scfm (m 3 /min) 9,111 (258) 8,687 (246) air flow required for rad. cooled unit: *scfm (m 3 /min) 135,369 (3,833) 135,369 (3,833) air flow required for heat exchanger/remote rad. based on 25f rise: *scfm (m 3 /min) 30,384 (866) 28,431 (810) * air density = 0.0739 lbm/ft 3 (1.184 kg/m 3 ) // exhaust system standby prime gas temp. (stack): f (c) 1,013 (545) 914 (490) gas volume at stack temp: cfm (m 3 /min) 26,062 (738) 22,884 (648) maximum allowable back pressure: in. h 2 0 (kpa) 34.1 (8.5) 34.1 (8.5) a pplication data
4 /// / 3250-xc6 dt 2 ? mtu onsite energy. subject to alteration due to technological advances. 2009-05 // t ognum g roup companies: europe / m iddle east / africa / latin america / mtu onsite energy / 88040 friedrichshafen / germany / phone + 49 7541 90 7060 / fax +49 7541 90 7084 / powergenregion1@mtu-online.com // asia / australia / pacifc / mtu onsite energy / 1, benoi place / singapore 629923 / republic of singapore / phone + 65 6861 5922 / fax + 65 6861 3615 / powergenregion2@mtu-online.com // u sa / canada / m exico / mtu onsite energy / 100 power drive / mankato, minnesota 56001 / usa / phone + 1 507 625 7973 / fax + 1 507 625 2968 / powergenregion3@mtu-online.com // worldwide for hot module / mtu onsite energy / 81663 munich / germany / phone + 49 89 203042 800 / fax +49 89 203042 900 / info@cfc-solutions.com //www.mtu-online.com emissions data no x + nmhc co pm 4.19 0.82 0.14 all units are in g/hp-hr and are epa d 2 cycle values. (plvvlrohhovrwhhlhpddudvdxfwlrrdpel - qpsudxuedurpulfsuxuxplglixosdqg txdollqdoodlrqsdudpupdxulqlquxpqdlrq fgddsurylggduoderudruuxoiurprqqlq usuqlqludlqgdddredlqgxqgufrq - uroogqylurqpqdofrqgllrqlfdoleudglquxpqdlrq udfdeorqlg6d1dlrqdoxudxri6dqgdug dqglqfrpsoldqfl63uxodlrqirxqgllq5 3dulgffoydoxiurpdfqlqlxdudq - greeor636dqgdugd63gqg frqgllrq r ating definitions and conditions // pelhwfdsdelolwdfwrudwwprvxowrxu orfdo0782vlwh(hu3rhu*hhudwlrlvwulexwruru rwhudowlwxghv // 6wdgeudwlvdssowrlvwdoodwlrvvhuhgeduholdeoh xlolrxufdqgeudlqldssolfdeorydulq ordgirugxudlrqridsrurxd1rryuordgfdsd - eloliruludlq5dlqdulqdffrugdqfl ,6266dqg,1 // 3ulphsrhuudwlvdssowrlvwdoodwlrvhuhxwlolwsrhu lvxddlodeohruxuholdeohwdulordgwhxpehur hhudwruvhwrshudwlrxuvlvxolplwhgrhuordg fdsdflwlvddlodeohrurhrxulwhoh5dwlvduhl dffrugdfhlw62rhuordgsrhuldffrugdfh lw6266dg1)ru olplwhguxlwlphdgedvhordgudwlvfrvxowwh idfru // hudwlr)dfwru altitude 1rsrhughfuhdvhlwlfuhdvhghohdwlrxs ripd0dsupldeo oydlrqliprqxoidfruirudolxg eqipdqgip t emperature 1rsrhughfuhdvhlwlfuhdvhglwdnhfrp - exlrqpsudxuxsrdip rqxoidfruirusuirupdqfdlupsudxu , 61,016,216 sound data u nit t ype standby full load standby n o load prime full load prime n o load opu w/critical grade mufer (dba) 108 100 106.5 100 system dimensions (l x w x h) weight (less tank) opu 306.38 x 114.13 x 130.5 in (7,780 x 2,900 x 3,310 mm) 63,264 lb (28,696 kg) drawing above for illustration purposes only, based on standard open power 480 volt generator. lengths may vary with other voltages. do not use for installation design. materials and specifcations subject to change without notice. weights and dimensions are based on open power units and are estimates only. consult the factory for accurate weights and dimensions for your specifc generator set. measurements for sound data are taken at 23 ft (7 m).


▲Up To Search▲   

 
Price & Availability of 3250-XC6DT2

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X