  specifications are subject to change without notice (21.10.00) 1 monitoring relays product description ordering key housing function type item number output power supply range ? trms ac/dc over or under current monitoring relays ? current measuring through external shunt or ct ? selection of measuring range by dip-switches ? measuring ranges from 6 to 150 mv ac/dc and 0.4 to 4 v p ac (mi or mp range) ? adjustable current on relative scale ? adjustable hysteresis on relative scale ? adjustable delay function (0.1 to 30 s) ? programmable latching or inhibit at set level ? output: 8 a spdt relay n.d. or n.e. selectable ? for mounting on din-rail in accordance with din/en 50 022 (dib02) or plug-in module (PIB02) ? 22.5 mm euronorm housing (dib02) or 36 mm plug-in module (PIB02) ? led indication for relay, alarm and power supply on ? galvanically separated power supply type selection mounting output supply: 24 vdc supply: 24/48 vac supply: 115/230 vac din-rail spdt dib 02 c 724 150mv dib 02 c b48 150mv dib 02 c b23 150mv plug-in spdt pib 02 c 724 150mv pib 02 c b48 150mv pib 02 c b23 150mv input voltage level dib02: terminals y1, y2 PIB02: terminals 5, 7 measuring ranges internal resis. max. volt. 6 to 60 mv ac/dc 1 k 2 v 15 to 150 mv ac/dc 1 k 2 v max. voltage for 1 s 15 v 0.4 to 4 v p ac 50 k 50 v max. voltage for 1 s 100 v mi and mp ct ranges aac rms max. curr. 1-ph.: 3-ph.: mi 5 mp 3005 0.5 to 5 a 20 aac mi 20 mp 3020 2 to 20 a 50 aac mi 100 mp 3100 10 to 100 a 250 aac mi 500 mp 3500 50 to 500 a 750 aac note: the input voltage cannot raise over 300 vac/dc with respect to ground (PIB02 only) 1-phase true rms ac/dc over or under current types dib02, PIB02 input specifications dib 02 c b23 150mv dib02 and PIB02 are precise trms ac/dc over or under current (selectable by dip- switch) monitoring relays. the current is measured through an external shunt. 1-phase and 3-phase current up to 500 aac can be monitored connecting mi or mp current transformers. owing to the built-in latch function, the on-position of the relay output can be maintained. inhibit function can be used to avoid relay operation when not desired (maintenance, transitions). the led's indicate the state of the alarm and the output relay. dib02 PIB02 note: mp3... current transformers not suitable for under cur- rent measurement due to the output signal of the device (see data sheet) contact input dib02 terminals z1, y1 PIB02 terminals 8, 9 disabled > 10 k enabled < 500 latch disable > 500 ms input specifications (cont.)
2 specifications are subject to change without notice (21.10.00) dib02, PIB02 mode of operation dib02 and PIB02 monitor both ac and dc over or under current through an external shunt. when connected with mi or mp current transformer (using the 0.4 to 4 v p range) they can monitor 1-phase or 3- phase ac current up to 500 a. example 1 (connection between termi- nals z1, y1 or 8, 9 - latching function enabled) the relay operates and latch- es in operating position when the measured value exceeds (or drops below) the set level for more than the set delay time. provided that the current has dropped below (or has exceeded) the set point (see hysteresis setting), the relay releases when the intercon- nection between terminals z1, y1 or 8, 9 is interrupted or the power supply is inter- rupted as well. the red led flashes until the delay time has expired or the measured value comes back to a non-alarm value (see hysteresis setting). example 2 (mi ct) (no connection between ter- minals z1, y1 or 8, 9 - latch function disabled) the relay operates when the current flowing in the ct exceeds (or drops below) the set level for more than the set delay time. it releases when the current drops below (or exceeds) the set level (see hysteresis set- ting) or when power supply is interrupted. example 3 (mp ct) (no connection between ter- minals z1, y1 or 8, 9 - latch function disabled - over cur- rent measurement) the relay operates when the maximum current flowing in the ct exceeds the set level for more than the set delay time. it releases when the maxi- mum current drops below the set level (see hysteresis setting) or when power sup- ply is interrupted. note when the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse before relay activation. power supply overvoltage cat. iii rated operational voltage (iec 60664, iec 60038) through terminals: a1, a2 or a3, a2 (dib02) 2, 10 or 11, 10 (PIB02) 724: 24 vdc 20%, insulated b48: 24/48 vac 15% 45 to 65 hz, insulated b23: 115/230 vac 15% 45 to 65 hz, insulated dielectric voltage dc supply ac supply supply to input 2 kv 4 kv supply to output 4 kv 4 kv input to output 4 kv 4 kv rated operational power ac 4 va dc 3 w supply specifications power on delay 1 s 0.5 s or 6 s 0.5 s reaction time (input signal variation from -20% to +20% or from +20% to -20% of set value) alarm on delay < 100 ms alarm off delay < 100 ms accuracy (15 min warm-up time) temperature drift 1000 ppm/c delay on alarm 10% on set value 50 ms repeatability 0.5% on full-scale indication for power supply on led, green alarm on led, red (flashing 2 hz during delay time) output relay on led, yellow environment (en 60529) degree of protection ip 20 pollution degree 3 (dib02), 2 (PIB02) operating temperature -20 to 60c, r.h. < 95% storage temperature -30 to 80c, r.h. < 95% housing dimensions din-rail version 22.5 x 80 x 99.5 mm plug-in version 36 x 80 x 87 mm weight approx. 150 g screw terminals tightening torque max. 0.5 nm acc. to iec 60947 ce-marking ye s general specifications output spdt relay rated insulation voltage 250 vac contact ratings (agsno 2 ) resistive loads ac 1 8 a @ 250 vac dc 12 5 a @ 24 vdc small inductive loads ac 15 2.5 a @ 250 vac dc 13 2.5 a @ 24 vdc mechanical life 3 30 x 10 6 operations electrical life 3 10 5 operations (at 8 a, 250 v, cos j = 1) operating frequency 7200 operations/h dielectric strength dielectric voltage 3 2 kvac (rms) rated impulse withstand volt. 4 kv (1.2/50 s) output specifications
specifications are subject to change without notice (21.10.00) 3 dib02, PIB02 function/range/level and time delay setting selection of measuring range: dip-switch selector (1 to 2) 1 2 0.4 to 4 v p input range 6 to 60 mv input range 15 to 150 mv input range selection of function: dip-switch selector (3 to 6) 3 relay de-energized in normal condition. relay energized in normal condition. 4 power on delay 6 0.5 s power on delay 1 0.5 s 5 contact input as latch func- tion enable. when the contact is closed, the latch function is activated. reset of the latch condition occurs when the con- tact is open or by power down. contact input as inhibit of alarm enable. when the con- tact is closed the relay remains in normal position even if the alarm condition occurs. 6 over current monitoring relay. the alarm condition occurs when the current input is over the set point value. under current monitoring relay. the alarm condition occurs when the current input is under the set point value. selection of level and time delay: upper knob: setting of hysteresis on rela- tive scale: 0 to 30% on set value. centre knob: current level setting on rela- tive scale: 10 to 110% on full scale. lower knob: setting of delay on alarm time on absolute scale (0.1 to 30 s). example 1 example 2 example 3 l n(-) pe z1 y1 y2 a1 a3 a2 15 16 18 i l n(-) pe z1 y1 y2 a1 a3 a2 15 16 18 i l n(-) pe z1 y1 y2 a1 a3 a2 15 16 18 i 24 vdc (+) 48/230 vac 24/115 vac 24 vdc (+) 48/230 vac 24/115 vac 24 vdc (+) 48/230 vac 24/115 vac latch/inhibit enable example 1 example 2 example 3 l n(-) pe 5 7 10 1 43 1 43 1 43 i 8 9 l n(-) pe 5 7 10 i 8 9 l n(-) pe 5 7 i 8 9 24 vdc (+) 48/230 vac 24/115 vac 11 2 24 vdc (+) 48/230 vac 24/115 vac 11 2 24 vdc (+) 48/230 vac 24/115 vac 11 2 latch/inhibit enable 10 wiring diagrams dib02 PIB02 on
4 specifications are subject to change without notice (21.10.00) operation diagrams power supply over current under current - latch function under current power supply latch on set level relay on red led on set level relay on red led on power supply red led on set level hysteresis hysteresis hysteresis relay on 1 or 6 s 1 or 6 s over current - inhibit function power supply inhibit on set level relay on red led on hysteresis 1 or 6 s 1 or 6 s dib02, PIB02