 Voltage Sensitive Relays
WILMARTM Protective Relays - D100X Series, Close Differential
Function:
* ANSI/IEEE C37.90-1978
* UL file No. E58048 * CSA file No. LR61158 Close Differential Relays are voltage sensitive. The pick-up and drop-out voltage settings are independently adjustable, which allows precise setting of the differential voltage. This relay is available in a wide range of AC and DC voltages. Their primary application is the sensing and control of transfer switches.
0.5
Operation:
See Part Number Selection
Monitors a single phase AC signal, and is used for undervoltage detection. Has separate pick-up and drop-out voltage settings, providing an adjustable hysteresis.
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
2.6 6 3.0 5 3.
2.2
50 3
11/64" DIA. 4 MTG. HOLES
PRODUCT SPECIFICATIONS
PART NUMBER SELECTION
Sample Part No. D100X
Height 2" 2" 3.125" 3.125" 3.125" 3.125" 3.125"
Part Number
Nominal Voltage ............................... Nominal Frequency .......................... Pick-Up Adjustment Range ............. Drop-Out Adjustment Range ........... Maximum Differential Setting .......... Minimum Differential Setting .......... Output Contacts ............................... Contact Ratings ................................ Operating Temperature Range ........ Expected Life ....................................
D100X
AC, Single Phase, see part number selection 50 to 400 Hz. 67-100% of nominal voltage 67-100% of nominal voltage 33% of nominal voltage 2% of nominal voltage Form C (SPDT) 5 Amp resistive at 120 VAC or 28 VDC -20C to +85C 10 million operations
Model: L-L Volts D100X = 120 VAC D100-6X = 120 VAC, Spike Suppression D100-3X = 208 VAC D100-4X = 240 VAC D100-8X = 277 VAC D100-5X = 480 VAC D100-7X = 510 VAC
Surge Withstand Capability is in compliance with the requirements of ANSI/IEEE C37.90B Notes: 1. Remove black nylon protective screws to gain access to the two internal adjustment potentiometers. 2. Clockwise rotation of the pick-up and drop-out adjustment will raise the voltage trip point. 3. The relay contacts are shown in the de-energized state. Consult factory for additional models.
Inverse Time Drop-Out: The differential relay contains a time delay before operation so that momentary voltage transients do not aftect the operation of the relay. The time delay has an inverse time characteristic so that excessive voltage conditions will cause a more rapid dropout. This time delay is approximately 200mSec. (12 cycles) at the trip settings and decreases to 30 mSec. at approximately 15% beyond the trip settings.
26
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)


▲Up To Search▲   

 
Price & Availability of D100-7X

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X