Part Number Hot Search : 
JAN2N AS1323 K3109 U8310A E005003 B2005 SDA12 CPZRL7
Product Description
Full Text Search
 

To Download ECM140US12 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 AC-DC
140 Watts ECM140 Series
* * * * * * * *
xppower.com
High Efficiency Resonant Topology 120/148 W - Convection/Forced-cooled Ratings Class I & Class II Installations 12 V Fan Output as Standard Remote Sense as Standard 5V Standby Option Remote On/Off & Power OK Signals Option IT, Industrial & Medical Safety Approvals
Specification
Input
* 80-264 VAC (120-370 VDC), derate output power <90 VAC (See derating curve) Input Frequency * 47-400 Hz (See note 1) Input Current * 2.5 A typical at 115 VAC, full load 1.3 A typical at 230 VAC, full load Inrush Current * 40 A max at 230 VAC, cold start (25 C) Power Factor * EN61000-3-2, class A Earth Leakage Current * 265 A at 264 VAC/60 Hz max. 0.5/1.1 mA 115/230 VAC at 400 Hz typ. Input Protection * Internal T5.0 A/250 V fuse in line and neutral Input Voltage
General
Efficiency Isolation Switching Frequency Signals (Option -A) MTBF * 88% typical * 4000 VAC Input to Output, 1500 VAC Input to Ground, 500 VAC Output to Ground * 70 kHz typical * Power OK - open collector, Remote On/Off, 5 V Standby * 220 kHrs per MIL-HDBK-217F
Environmental
Operating Temperature * 0 C to +70 C derate linearly from +50 C at 2.5%/C to 50% load at +70 C when convection-cooled and from +60 C at 2.5%/C to 75% load at +70 C when forced-cooled. See derating curve and longform datasheet for thermal considerations. Cooling * Convection & fan cooled ratings (see tables) Operating Humidity * 95% RH, non-condensing Storage Temperature * -40 C to +85 C Operating Altitude * 3000 m Shock * 30 g pk, half sine, 6 axis Vibration * 2 g rms, 5 Hz to 500 kHz, 3 axis
Output
Output Voltage Output Voltage Trim Initial Set Accuracy Minimum Load Start Up Delay Start Up Rise Time Hold Up Time Drift Line Regulation Load Regulation Over/Undershoot Transient Response * * * * * * * * * * * * 12-48 VDC (see tables) 5% 1% V1, 5% V2, 3% V3 0.1A required for V2 regulation when used. 1 s typical 50 ms 16 ms min at 115 VAC 0.2% after 20 min warm up 0.5% max 1% V1, 5% V2 & V3 max 5% typical 4% max. deviation, recovery to within 1% in 500 s for a 50-75-50% load change 1% pk-pk V1, others 2%, 20 MHz bandwidth 115-140% Vnom, recycle input to reset 110-150% V1 only Continuous trip and restart (Hiccup mode) 0.05%/C
EMC & Safety
Low Voltage PSU EMC * EN61204-3, high severity level as below Emissions * EN55022 level B conducted EN55022 level A radiated Harmonic Currents * EN61000-3-2, class A Voltage Flicker * EN61000-3-3 Radiated Immunity * EN61000-4-3, level 3 Perf Criteria A EFT/Burst * EN61000-4-4, level 3 Perf Criteria A Surge * EN61000-4-5, installation class 3 Perf Criteria A Conducted Immunity * EN61000-4-6, level 3 Perf Criteria A Dips & Interruptions * EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms, Perf Criteria A, B, B, EN60601-1-2, 30% 500 ms, 60% 100 ms, 100% 10 ms, 100% 5000 ms, Perf Criteria A, A, A, B - 230 VAC. Consult longform datasheet for 115 V operation. Safety Approvals * See Safety Approvals (see next page) Equipment Protection * Class I and Class II Class
Ripple & Noise Overvoltage Protection Overload Protection Short Circuit Protection Temperature Coefficient Remote Sense Remote On/Off (Inhibit/Enable Option -A) Notes
* * * * *
* Compensates for 0.5 V total voltage drop * Uncommitted isolated optocoupler diode, powered diode inhibits V1 & V2
1. Safety approvals cover frequency 47-63 Hz.
AC-DC
Models and Ratings - Convection-cooled
Output Power(1) 120 W 120 W 120 W 120 W 120 W Output Voltage V1 12.0 VDC 15.0 VDC 18.0 VDC 24.0 VDC 48.0 VDC Max Output Current V1 10.0 A 8.0 A 6.6 A 5.0 A 2.5 A Fan Output V2 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A Standby Supply V3 (optional) 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A
ECM140
Model Number(2,3) ECM140US12 ECM140US15 ECM140US18 ECM140US24 ECM140US48
Notes
1. Convection-cooled, max output power must not exceed 120 W for combined V1, V2, & V3 2. For V3 5 V standby, Power OK & Inhibit, add suffix `-A' to model number. 3. For covered versions, add suffix `-C' to model number or order part no. ECM140 COVER KIT for standalone cover. Not suitable for use in class II installations.
Models and Ratings - Forced-cooled
Output Power(1) 148 W 148 W 148 W 148 W 148 W Output Voltage V1 12.0 VDC 15.0 VDC 18.0 VDC 24.0 VDC 48.0 VDC Max Output Current V1 11.7 A 9.3 A 7.7 A 5.8 A 2.9 A Fan Output V2 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A 12.0 V/0.5 A Standby Supply V3 (optional) 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A Model Number(2) ECM140US12 ECM140US15 ECM140US18 ECM140US24 ECM140US48
Notes
1. 10 CFM airflow. 2. For V3 5 V standby, Power OK & Inhibit, add suffix `-A' to model number.
Mechanical Details
5.00 (127.0) 0.22 (5.7) 4.55 (115.6) 0.20 (5.1) 1.30 (33.0)
Input Connector J1 Pin 1 Line Pin 2 Neutral .25" Faston Earth
J1 mates with Molex housing 09-50-1031 and Molex series 5194 crimp terminals.
3.00 (76.2) 1.90 (48.3) 2.55 (64.8) 0.61 (15.6) 0.23 (5.7) 0.20 (5.1) 0.25 Faston Ground Tab V Adj. 0.14 (3.5) 0.18 (4.6) 1.11 (28.3)
2.50 (63.6)
0.19 (4.8) SMD component height
Output Connector J2 Pin Single 1 +V1 2 +V1 3 +V1 4 +V1 5 RTN 6 RTN 7 RTN 8 RTN J2 mates with Molex housing 09-50-1081 and Molex series 5194 crimp terminals. Fan Connector J4 Pin 1 Fan +(12V) Pin 2 Fan J4 mates with Molex housing 22-01-1024 and Molex series 5103 crimp terminals.
4 x o0.156 (3.96) Mounting Holes o0.312 (7.92) Clearance Top & Bottom
Pin 1 2 3 4 5
Signal Connector J3 Single Pin Single +5V Standby* 6 Inhibit LO* Logic GND* 7 +Sense Logic GND* 8 -Sense Power OK* 9 +Vout Inhibit HI* 10 -Vout
*Optional J3 mates with JST housing PHDR-10VS and JST series SPHD-001T-P0.5 crimp terminals.
Notes
1. All dimensions in inches (mm). Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25) 2. Cover dimensions are 5.50 x 3.50 x 1.54 (140 x 89 x 39). See longform datasheet for drawing.
Derating Curves
148
Safety Approvals
Force-cooled >10 CFM
120
148
10 CFM Force-cooled
Output Power (W) 120
Output Power (W)
111 96
Convection-cooled
IEC60950-1 CB report, CSA 22.2 No. 60950-1, UL60950-1, TUV EN60950-1 IEC60601-1 CB report, CSA 22.2 No. 60601-1, UL60601-1, TUV 60601-1,
+50 +60 +70
100 84
Convection-cooled
60
60
Convection-cooled with cover
42
Convection-cooled with cover
80
90 Input Voltage (VAC)
264
0
+40
TUV IEC61010-1
Ambient Temperature (C)
01-Jul-08


▲Up To Search▲   

 
Price & Availability of ECM140US12

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X