Part Number Hot Search : 
GMZJ18 SC538 GMS90C31 LF8411 X28HC256 002000 74LV126 UESP10D
Product Description
Full Text Search
 

To Download T1K16TA Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Terminator I/O Specifications
AC OUTPUT MODULES
T1K-08TA T1K-16TA <---> <--->
Specifications
Outputs per Module Commons per Module Operating Voltage Range Output Voltage Range Max. Load Current ON Voltage Drop Max. Leakage Current Max. Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Required Status Indicators Error Status Indications(LEDs ) Fuses (User Replaceable) T1K-FUSE-1 Weight
8 2 (4 pts. / common) isolated 17-240 VAC (47-63Hz) min./max. 15-264 VAC (47-63Hz) min./max. 1A / pt., 4A / common (subject to derating) 1.5VAC @ > 50mA, 4.0VAC @ < 50mA 4mA @ 264 VAC 10A for 10ms 10mA < 1ms < 1ms + 1/2 cycle 250mA @ 5VDC Logic side FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown 2, (10A, 250V / common) 5 x 20 mm type 140g FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown 4, (10A, 250V / common) 5 x 20 mm type 190g 450mA @ 5VDC
T1K-08TA
16
T1K-16TA
FIELD I/O
8-point and 16-point, AC output modules
The 8-point AC module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point AC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.
4 (4 pts. / common) isolated
Equivalent Output Circuit
w
w
w
.D
at aS
he
et 4U .c
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
om
Universal Field I/O
7-41
www..com
Terminator I/O Dimensions and Installation
DIMENSIONS AND INSTALLATION
It is important to understand the installation requirements for your Terminator I/O system. This will help ensure that the Terminator I/O products work within their environmental and electrical limits.
See the Enclosures section of this desk reference for an enclosure that may be suitable for your application
Plan for safety
This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (It is also available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Unit dimensions and mounting orientation
Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units can be mounted horizontally or vertically. However, to insure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2" depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
Terminator I/O Environmental Specifications
Ambient Operating Temperature Storage Temperature Ambient Humidity Atmosphere Vibration Resistance Shock Resistance Voltage Withstand (Dielectric) Insulation Resistance Noise Immunity Agency Approvals
32F to 131F (0C to 55C) -4F to 158F (-20C to 70C) 5% to 95% (Non-condensing) No corrosive gases. The level of environmental pollution = 2 (UL 840) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 1500VAC, 1 minute 500VDC, 10M NEMA ICS3-304 Impulse noise 1s, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) UL, CE, FCC class A, NEC Class 1 Division 2
48mm (1.89in)
48mm (1.89in)
48mm (1.89in)
89mm (3.5in)
83.3mm (3.28in)
80mm (3.15in)
80mm (3.15in)
80mm (3.15in)
80mm (3.15in)
Power Supply
Network Interface Module
Half-size I/O Module with Base
Full-size I/O Module with Base
System Depth
7-14
Universal Field I/O
1 - 80 0 - 633 - 0405
Terminator I/O Installation
I/O MODULE
I/O module installation
Terminator I/O modules feature separate terminal bases for easy installation. To install I/O modules:
1. Slide the module into its terminal base (until it clicks into position) 2. Hook upper DIN-rail tabs over the top of DINrail, and press the assembly firmly onto the DIN-rail. 3. Slide the module along the DIN-rail until it engages with the adjacent module.
1
DN-ASB angled mounting bracket
Great for mounting in upper locations
FIELD I/O
Great for mounting in lower locations
2 3
Optional angled support bracket raises and tilts the mounting rail for easier access and wiring. Use with 35mm DIN rail. See the Connection Systems in this catalog for details.
Removing I/O modules is a snap
Grip the locking handle, as shown, and pull gently to eject the I/O module from its base. The module will slide out for easy replacement. This procedure does not apply to network interface modules or power supplies, which have integral bases.
Hot swappable I/O modules
You can remove I/O modules under power, but exercise caution while doing so. Do not touch the terminals with your hands or any conductive material. Always remove power when possible.
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O
7-15
Terminator I/O Specifications
POWER SUPPLIES AND POWER REQUIREMENTS
Power supplies
The Terminator I/O product line offers two power supply options: AC or DC. The power supplies are always positioned to the left of the modules to which they supply power. Consult the system configuration examples and the power budgeting example for more information on positioning power supplies.
Power requirements
Module
T1H-EBC T1H-EBC100 T1H-PBC T1K-DEVNETS T1K-RSSS T1K-MODBUS
5VDC 24VDC
0 0 0 45 0 0
Module
T1H-08TDS T1K-08TD1 T1K-16TD1 T1K-08TD2-1 T1K-16TD2-1
5VDC 24VDC
Module
T1F-08AD-1 T1F-08AD-2 T1F-16AD-1 T1F-16AD-2 T1F-14THM T1F-16RTD
5VDC 24VDC
Interface Modules
350 300 530 250 250 300
DC Output Modules
200 100 200 200 200 0 200* 400* 0 0
Analog Input Modules
75 75 75 75 60 150 50* 50* 50* 50* 70* 0
AC Output Modules
T1K-08TA 250 450 300 0 0 0 T1K-16TA T1K-08TAS
DC Input Modules
T1K-08ND3 T1K-16ND3 35 70 0 0
Analog Output Modules
T1F-08DA-1 T1F-08DA-2 T1F-16DA-1 T1F-16DA-2 75 75 75 75 75* 75* 150* 150*
Power supply specifications
T1K-01AC <---> T1K-01DC <---> Power Supply Specifications
Input Voltage Range Input Frequency Maximum Power
AC Input Modules
T1K-08NA-1 T1K-16NA-1 35 70 0 0
Relay Output Modules
T1K-08TR T1K-16TR T1K-08TRS 350 700 400 0 0 0
Combination Analog Modules
T1F-8AD4DA-1 T1F-8AD4DA-2 75 75 60* 70*
Specialty Modules
T1H-CTRIO 400 0 * Use either internal or external source for 24VDC
* Use either internal or external source for 24VDC
110/220VAC 12/24VDC 50/60Hz 50VA N/A 30W 10A
Calculating the power budget
To calculate the power budget, read the available power (current rating) from the Power Supply Specifications table and subtract the power consumed by each module to the right of the power supply. Do not include modules to the right of an additional power supply.
T1K-01AC T1H-EBC T1K-16ND3 T1K-16TD2
Power Budget Example
Module 5VDC
+2000mA -350mA -70mA -200mA -75mA +1305mA
24VDC
+300mA -0mA -0mA -0mA -50mA +250mA
Max. Inrush Current 20A Insulation Resistance Voltage Withstand
Voltage
> 10M @ 500VDC 1 min. @ 1500VAC between primary, secondary and field ground 5.25VDC 2000 mA max below) 5.25VDC
T1F-08AD-1 Remaining
5VDC Current Rating (see current 2000 mA max option note PWR
Ripple Voltage
5% max. 24VDC 5% max. N/A
Adding additional power supplies
Each power supply furnishes power only to the network interface and I/O modules to its right. Inserting a second power supply closes the power loop for the power supply to the left, while also powering the modules to its right. Perform a power budget calculation for each power supply in the system.
24VDC PWR Fuse
300mA max. Current Rating (see current N/A option note below)
Accessories available for Terminator I/O are listed in the Terminator Field I/O section of the Price List
Ripple
10% max.
N/A
1 (primary), not replaceable
Note: 500mA @ 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA .
This power supply powers the network interface module and This power supply powers these three I/O the next two I/O modules modules
7-16
Universal Field I/O
1 - 80 0 - 633 - 0405
Terminator I/O Specifications
EXPANSION I/O CONFIGURATIONS
Expansion cables
T1K-10CBL <---> T1K-10CBL-1* <---> Right side to left side expansion cable
The T1K-10CBL(-1) connects the right side of an I/O base to the left side of the next I/O base. A maximum of two T1K-10CBL(-1) cables can be used per expansion system.
T1K-05CBL-LL T1K-05CBL-LL-1* Left side to left side expansion cable
<---> <--->
T1K-05CBL-RR <---> T1K-05CBL-RR-1* <---> Right side to right side expansion cable
The T1K-05CBL-RR(-1) connects the right side of an I/O base to the right side of the next I/O base. A maximum of one T1K-05CBL-RR(-1) cable can be used per expansion system. Note: When this cable is used, the expansion I/O assignments are from right to left (reversed).
FIELD I/O
The T1K-05CBL-LL(-1) connects the left side of an I/O base to the left side of the next I/O base. Only one T1K-05CBL-LL(-1) cable can be used per expansion system and must be used with a T1K-05CBL-RR(-1) cable. This cable cannot be connected to
the left side of the network interface base.
Cable length = 1.0m
Cable length = 0.5m
Cable length = 0.5m
*Note: The (-1) versions of the expansion cables pass 24VDC through on an isolated wire. (All cables pass the 5VDC base power.) Any local expansion DC input modules configured for "internal power" (current sourcing) must either have a power supply preceding it on the same base or, have a (-1) version cable pass 24VDC from a power supply on the preceeding base.
Using two T1K-10CBL expansion cables
In the system below, power supplies can be used anywhere.
Using T1K-10CBL expansion cable and T1K-05CBL-RR expansion cable
Power supplies can be used anywhere in the first two bases, but not in the last expansion base.
T1K-10CBL(-1)
I/O Addressing I/O Addressing
A power supply can be used on either base. T1K-10CBL(-1)
T1K-10CBL(-1)
A power supply cannot be used on a base that is connected to a system by aT1K-05CBL-RR(-1).
T1K-05CBL-RR(-1) See Note above
Using T1K-05CBL-RR expansion cable and T1K-05CBL-LL expansion cable
Power supplies can be used anywhere in the first and third bases, but not in the second base.
Do not connect a T1K-05CBL-LL(-1) to the left side of the network interface base.
Using T1K-05CBL-RR expansion cable
Power supplies can be used anywhere in the first base, but not in the second base
I/O Addressing I/O Addressing T1K-05CBL-RR(-1) See Note above
T1K-05CBL-RR(-1) See Note above
T1K-05CBL-LL
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR(-1).
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O
7-17
Terminator I/O Specifications
FIELD DEVICE WIRING AND POWER OPTIONS
Terminal base specifications
Terminator I/O terminal bases are available in screw clamp and spring clamp versions for both half-size and full-size modules. Hot stamp silkscreen labeling is used for numbering I/O points, commons, and all power terminals. Terminal Base Specifications
Terminal Type
Screw type Spring clamp n/a Solid: 25-14 AWG Stranded: 26-14 AWG
T1K-08B <--->
T1K-08B-1 <--->
Screw clamp, half-size
Spring clamp, half-size
T1K-16B <--->
T1K-16B-1 <--->
Recommended 1.77-3.54 lb-in (0.2 - 0.4 Nm) Torque Wire Gauge
Solid: 25-12 AWG Stranded: 26-12 AWG
Field device wiring options
Power your DC input devices from the integrated 24VDC power supply bus. T1K-08ND3 and T1K-16ND3 DC input modules include jumpers for selecting the internal 24VDC power supply available for 2 and 3-wire field devices. Clearly labeled triple stack terminals make it easy to wire 2 and 3wire devices ensuring clean wiring with only one wire per termination. External user supplied 24VDC power, or auxiliary 24VDC terminals from T1K-01AC, can be easily applied directly to one end of the terminal rows and jumpered across each base in the system. This is a convenient solution for powering analog I/O and discrete DC output devices whose modules do not have direct access to the internal bussed 24VDC. If current consumption increases, simply add additional T1K-01AC power supplies into the system.
2 and 3-wire DC input devices using bussed 24VDC power Screw clamp, full-size Spring clamp, full-size
Hot swap feature
The "hot swap" feature allows Terminator I/O modules to be replaced while system power is on. Be careful not to touch the terminals with your hands or other conductive material to avoid the risk of personal injury or equipment damage. Always remove power if it is equally convenient to do so.
Use externally supplied 24VDC power or 24VDC auxiliary power from T1K-01AC
Do not jumper modules together to create a 24VDC bus when using the "hot swap" feature. See Note below.
Note: Before "hot swapping" analog or DC output modules in a Terminator I/O system, make sure that each of the analog and DC output module's 24VDC and 0VDC base terminals are wired directly to the external power supply individually. If the external 24VDC/0VDC is
jumpered from base to base in a daisy chain fashion, and an analog or DC output module is removed from its base, the risk of disconnecting the external 24VDC/0VDC to the subsequent I/O modules exists.
7-18
Universal Field I/O
1 - 80 0 - 633 - 0405


▲Up To Search▲   

 
Price & Availability of T1K16TA

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X